Why an outdoor socket keeps tripping
The RCD switches off when it detects current leaking to earth, and outside that leak is nearly always physical. Water is the usual cause: a lid left open, a perished seal, a cable entering from the top of the box, or a dripping hosepipe tap beside the socket. That is why the trips often follow heavy rain and stop once things dry out.
Next comes cable damage. Buried runs get hit by spades, fence posts and edging tools, and rodents chew cable in garages. Then there is equipment: a mower, pond pump or pressure washer with water in the motor, or an indoor extension lead left on wet grass, will trip a healthy circuit.
Outside socket not working but nothing has tripped
A dead socket with every switch still on usually means a broken connection, not leakage. Corroded terminals, a blown fuse in an indoor spur, a switch someone has turned off or burnt socket contacts can all cut the supply. We work back from the socket to the source until the break is found.
Low-voltage garden lighting runs from a transformer. If every light goes out and nothing trips, the transformer or timer is the usual cause; if only part of the run fails, the fault is usually in a connector or joint. Mains-voltage spike lights and bollards are wired like any other circuit, and water in one fitting can trip the whole lot. We test each light and joint so only the faulty one is replaced.
Garage electrics keep tripping or shed electrics not working
Garages and sheds are usually fed by a cable from the house, often armoured, with a small consumer unit at the far end. When the house and garage boards both have 30 mA RCDs, one fault can trip either, so it looks like a house problem. Freezers and old tools are common culprits. When shed electrics stop working altogether, we test the supply cable and the outbuilding circuits separately to show whether the fault is in the ground or the building.
What we test on an outdoor circuit
- Insulation resistance, whole run then section by section
- Continuity of protective conductors, including the cable armour
- Polarity at sockets, switches and fittings
- Earth fault loop impedance
- RCD trip time
- The buried cable route, traced with a locator
Outdoor electrical repairs we carry out
A water-damaged socket is replaced with a weatherproof accessory, typically IP66 where it faces driving rain or a pressure washer, with the cable entering from below. A damaged buried cable is exposed by hand once traced, then re-jointed with a sealed kit or replaced in a short section. Where the garden shares an RCD with half the house, we may suggest moving it onto its own RCBO, priced separately and fitted only if you agree.
When a repair turns into planned work
Sometimes testing shows the outdoor wiring was never suitable, such as indoor cable buried without protection or a garage fed from an extension lead. We make it safe on the night, then quote new outdoor points and garden lights through our sockets and lighting service, or a new outbuilding supply through our new circuits service.